The service
technician reviews the
maintenance and
hydrostatic test records.
Any extinguishers
due for the 6-year
teardown or
hydrostatic testing are removed so that the work can be done. Any fire
extinguisher that is removed from a
building for
repair, internal maintenance,
or hydrostatic
testing must be replaced
by a fire
extinguisher that is appropriate
and rated for the
hazard.
A thorough
examination of the condition
of the
extinguisher cylinder is conducted
to check for
corrosion, dents,
gouges, and
repairs. If corrosion, dents,
or gouges are
identified, an evaluation
is made to
determine whether the problem
areas are within
tolerable ranges
or whether the
extinguisher needs
to be replaced.
Tolerances for corrosion,
dents, and gouges
are provided in
NFPA 10. Any
extinguisher that shows
signs of being
repaired such as welding
is replaced.
An evaluation is
conducted as the
pull pin is being
removed. A pin that
does not slide out
easily is replaced.
Additionally, the
pin and the slot are
examined. A bent
or corroded pin is
replaced. With the
pin out, the valve
stem is examined
to make sure that it
protrudes out the
top of the valve and
is correctly
extended. The valve stem is
also checked for
corrosion and damage.
A valve stem
problem typically necessitates
the teardown of
the extinguisher
and the
replacement of the valve stem.
The handle and the
actuation lever
are examined. Bent
or corroded handles
or levers and
rivets that cause the lever
to stick are
reasons for extinguisher removal for repair. A new tamper seal
is installed when
the pull pin is inserted
in the
extinguisher lever. The new tamper seal is not only required, but it gives
the building owner or a fire inspector a visual indication that the pull
pin, valve stem, handle, and lever evaluations were most likely conducted
during maintenance.
The pressure gauge is checked
to